April 13th 2009 Firmware Release: ASIC/1-6000 FW600a1.9 Zone Control Mode
ASIC/1-6000 FW600a1.9 supports an improved sequence to determine the Zone Control Mode: Heating, Cooling or Deadband. The controller:
Other changes in this release include:
For more information and documentation go to the ASIC/1-6000 page.
April 10th 2009 Firmware Release: ASIC/1-8800 Single, Dual Duct and Tracking VAV
Firmware 880a1.0 for the ASIC/1-8800 has been released for production. A limited number of prototype ASIC/1-8800 Dual Duct and Tracking VAV Controllers are available for field trials. If you would like to evaluate the ASIC/1-8800 or upgrade your prototype to the latest firmware, please contact technical support.
For more information and documentation go to the ASIC/1-8800 page.
Dec 9th 2008
New Product Announcement: WS-MOD Digital Wall Sensor
The WS-MOD Digital Display zone temperature sensor is used in conjunction with the
ASIC/2-7540 or ASIC/2-8540 controllers for measuring ambient zone temperature,
for displaying and modifying the Temperature Setpoint, and for initiating
afterhours operation.
The wall mounted sensor utilizes a precision thermistor to measure and display the zone temperature. The thermistor's high change of resistance creates a large signal that eliminates lead wire resistance problems. The information from the WS-MOD is polled on the local bus of the ASIC/2 controller using Modbus protocol.
The WS-MOD will be available for order in early 2009.
For more information and documentation go to the ASI Sensor page.
Nov 19th 2008 New firmware ASIC/1-6000 FW600a 1.8 has been released for field evaluation. br> A new proportional plus integral airflow control algorithm improves the approach to airflow setpoint. As the damper drives the airflow toward the setpoint, the output begins to pulse, in 1/6 s increments. The smallest non-zero Airflow Hysteresis gives the fastest approach to setpoint. As control approaches the setpoint, the airflow error is summed over time. The Airflow Integration Time [Typical 4] is the time required for a 25 ft/min error to sum to give an additional pulse. To enable this algorithm you must give the Airflow Integration Time a non-zero value.
Other updates include: Single Setpoint Deadband for WS-051; Word values of Input 2 and 3 now report correctly; and Dual Heating now works with Electric Heat personalities (FW600a1.7).
Nov 6th 2008 Recent updates include: Improved performance with ASIC/1-6000 controllers; Added support for 1200 baud; and ability to flash the forthcoming ASIC/1-8800 firmware. FlashDev-2008.zip is available for download and includes the lastest firmware for the ASIC/2-7540, ASIC/2-8540, ASIC/1-6000, and ASIC/1-8655 controllers.
Sept 30th 2008 WebLink 3.0 is released. ASI WebLink 3 is the next generation webserver for OPC networks which combines the features of WebLink 2 and ASI Monitor. It includes the following enhancements.
June 03rd 2008 New firmware, ASIC/1-8655 FW655a2.1 is available which fixes bugs and adds several new features.
May 21st 2008 New firmware, ASIC/1-6000 FW600a1.6 is available which fixes a problem with Input Types 148,149 ZT10kType 2 and with 164, 165 ZT10kType3 not being recognized as Zone Temperature. This was causing all the outputs to lock out.
February 1st 2008 New firmware, ASIC/2-7540 FW754a2.3 and ASIC/2-8540 FW854a2.3, is available which adds two new features to the Encode object.